Liquid Level Controllers, Electronic Type

1. NATIONAL Liquid Level Controller
Standard type, 220/380V 50Hz
With: Control Unit 21F-G
Probe Fitting PS-3R (with 10K ohms resistor)
3 Pcs Electrodes (probe rods)

Available Separately:
Control Unit 21F-G
Fitting PS-3R
Probe/Electrode

2. NATIONAL Liquid Level Controller
For High Temperature (150C) and high pressure upto 10 kgf/cm
With 3 Pcs Hi Temp fitting

High Temp. fitting AF6121 separately available


APPLICATION:
Automatic Level Control of Elevated Tank or Drain Reservoir
Suitable for Control of:
Single Phase 220V 50Hz Motor (Pump-Motor) OR
Three Phase 380/415V 50Hz Motor (Pump-Motor)

SPECIFICATIONS:
• Control Capacity : 5A 250VAC
• Electrical Life : More than 0.5 Million operations
• Tolerance of rated voltage : ± 15%
• Built-in surge arrester circuit
• Controller with GOLDEN Bridge Circuit.

INSTRUCTIONS:

  • The Standard controller is to be used as 2-wire type, therefore connect the given 10K ohms resistor between the E1 and E2 terminals inside Probe Fitting PS-3R. Then make two wire connections, one each from E1 and E3 Electrode terminals in PS-3R to the control unit 21F-G.
  • The High Temperature & High Pressure type Controller is to be used as 3-wire type, hence make three wire connections, one from each high T/P Probe fitting AF6121 to the control unit 21F-G.
  • For using above controller for control of 3-phase motor please refer to the wiring diagram inside the cover of the control unit 21F-G.
  • Use supply terminals S0 & S1 for 220VAC or S0 & S2 for 380/415V 50Hz inside control unit 21F-G.
  • For mounting Probe Fitting PS-3R make a hole of 54mm dia in tank or use a coupling of 54mm dia.
  • Cut the Electrode E1 as per your upper level control requirement before fitting.
  • Electrode E2 controls the lower level and the size may be cut if required.
  • Electrode E3 should always be longer than or equal to the Electrode E2.