1. POWER FACTOR CONTROLLER: Digital/6-Steps
With Continuous Digital Power Factor Display
Type : B6 6 Steps

SPECIFICATIONS:

i. Power Supply & Measurement voltage: 230V±15% OR 400V±15%
ii. Connection : with or without Neutral Line i.e. LN=Phase to Neutral or LL=Phase to Phase
iii. Frequency : 50 or 60Hz ± 1Hz, automatic selection
iv. Operation Sequence : user selectable from menu
normal 1: 2: 4: 4; stack 1: 1: 1: 1:
circulating A 1: 1: 1: 1; circulating B 1: 2: 2: 2:
v. Output Relay : N.O., Contact Ratings: 2.0A/400VAC
vi. Alarm Relay : N.O., Contact Ratings: 2.0A/400VAC
vii. Ambient Temperature : 0 to 50C
viii. Size : 144 x 144 x 60mm, Protection Class : IP40
ix. Step Reconnection Delay : Adjustable from 10 to 300 secs

FEATURES:

  • Three digit LCD Display with graphical symbols for continuous display of Power Factor and setting & display of 8 different functions selection modes.
  • Automatic search of C/K values. C/K setting and display 0.00 … 1.99.
  • Easy to use menu-driven user interface.
  • Automatic Polarity adjustment of CT connection.
  • Separate alarm relay with potential free terminals.
  • All steps are released at voltage dropout.
  • Number of steps setting and display 1 … 6.
  • Manual stepping setting and display.
  • Plug in connectors at rear side.
  • State of art microprocessor technology.

2. POWER FACTOR CONTROLLER: Digital/12 Steps with Alarms
with Continuous Digital Power Factor & Capacitor Steps Display.
Type : A12 12 Steps


SPECIFICATIONS:

i. Power Supply : 230V±15%
ii. Measurement Voltage : 230V±15% OR 400V±15%
iii. Connection : with or without Neutral Line i.e. LN=Phase to Neutral or LL=Phase to Phase
iv. Frequency : 50 or 60Hz ± 2Hz, automatic selection.
v. Operation Sequence : user selectable from menu
normal 1: 2: 4: 4; stack 1: 1: 1: 1:
circulating A 1: 1: 1: 1; circulating B 1: 2: 2: 2:
vi. Output Relay : N.O., Contact Ratings: 2.0A/400VAC
vii. Alarm Relay : N.O., Contact Ratings : 2.0A/400VAC
viii. Accuracy Class : 1.5%
ix. Ambient Temperature : 0 to 50C
x. Size : 144 x 144 x 60mm, Protection Class : IP40
xi. Step Reconnection Delay : Adjustable from 10 … 900 secs.

FEATURES:

  • 16 Character alphanumeric LCD with graphical symbols, for continuous display of Power Factor and Capacitor steps.
  • Power Factor display 0.00 ind. … 1.00 … 0.00 cap.
  • LED display for alarm and ind/cap.
  • CT ratio settings and display : 100/5 … 6000/5.
  • Target PF setting and display : 0.80 ind … 1.00 … 0.90 cap.
  • Setting and display of step sizes : 10 … 1000 KVAR
  • Setting and display of input voltage : 80 … 460V.
  • Automatic search of C/K values. C/K setting and display 0.00 … 1.99.
  • Easy to use menu-driven user interface.
  • Automatic Polarity adjustment of CT connections.
  • Separate alarm relay with potential free terminal.
  • Following Alarms can be selected (enable/disable and status) low power factor, hunting, abnormal cos ø, undervoltage, overcapacitive, wrong frequency, overcurrent, overvoltage, overtemperature, voltage harmonic distortion (THD), capacitor overload and capacitor output low.
  • All steps are released at voltage dropout.
  • Number of steps setting and display 1 … 12.
  • Manual stepping setting and display.
  • Fixed stepping setting and display.
  • Plug in connectors at rear side.
  • State of art microprocessor technology.

Also available:

Type: B12/12 Steps
With Continuous Power Factor & Capacitor Steps Display
(Note: B12 is same as Type A12, but without Alarm function)